Firouzjah Khalil Gorgani – Faculty of Electrical and Computer Engineering Nushirvani Technical University of Babol Babol-Iran
Fateme Heydari – Faculty of Electrical and Computer Engineering Nushirvani Technical University of Babol Babol-Iran
Abdolreza Sheikholeslami, – Faculty of Electrical and Computer Engineering Nushirvani Technical University of Babol Babol-Iran

چکیده:

This paper presents an accurate method fordiscrimination between transformer inrushcurrent and power system fault. Analysis ofthe waveform of the current transient signaland calculated flux at the secondary windings is performed in order to determine whether the current is a fault or a magnetizing inrush current. Due to the symmetrical relation between the inrush current and related flux (at three phase), the proposed algorithm deals with a morphological technique in detection process. The proposed discriminator criterion is tested by various types of magnetization curves, different energization times and several various power system faults. The MATLAB/EMTP simulation results show that the proposed technique offers fastresponses (half power frequency cycle) in protection and accurately discriminate between the magnetizing inrush current and power system faults.